Insulated Adaptors provide a means to isolate the earth of the supply cable from the
load equipment thus reducing the risk of damage to electronic equipment. The adaptor
incorporates a Nylon 6 dielectric insulator between the metallic male thread entering the
equipment and the metallic female thread receiving the cable gland.
Cable gland and cable can still be earthed externally with the use of an earth tag fitted
between the cable gland and the Insulated Adaptor.
• An IP rating of IP66 /67/68 is maintained.
Hazardous: IECEx: Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex tb IIIC Db
ATEX: Exd IIC Gb, Ex e II Gb, Ex tb IIIC Db
Certification: IECEx CML 16.0056X IEC 60079-0, IEC 60079-1, IEC 60079-7
IEC60079-15, IEC60079-31
IEC 60529
ATEX CML15ATEX1040X EN 60079-0, EN 60079-1, EN 60079-7,
EN 60079-31
London Underground Approval: 3043 LU 1-085
IP Protection: IP66 / IP68 (2m) IEC 60529
Temperature Range: -20°C to 95°C
Material: Brass / Nickel Plated Brass
Insulator Material: Nylon 6